Detalhes do Documento

On-line diagnostics of transformer winding insulation failures, by Park`s vecto...

Autor(es): Oliveira, L. M. R. cv logo 1 ; Cardoso, A. J. Marques cv logo 2

Data: 2002

Identificador Persistente: http://hdl.handle.net/10400.1/27

Origem: Sapientia - Universidade do Algarve

Assunto(s): Máquinas eléctricas


Descrição
This paper presents a non-invasive approach for diagnosing winding insulation failures in three-phase transformers, which is based on the on-line monitoring of the primary and secondary current Park's Vector. Experimental and simulated results demonstrate the effectiveness of the proposed technique, for detecting winding inter-turn insulation faults in operating three-phase transformers.