Document details

On-line diagnostics of transformer winding insulation failures, by Park`s vecto...

Author(s): Oliveira, L. M. R. cv logo 1 ; Cardoso, A. J. Marques cv logo 2

Date: 2002

Persistent ID: http://hdl.handle.net/10400.1/27

Origin: Sapientia - Universidade do Algarve

Subject(s): Máquinas eléctricas


Description
This paper presents a non-invasive approach for diagnosing winding insulation failures in three-phase transformers, which is based on the on-line monitoring of the primary and secondary current Park's Vector. Experimental and simulated results demonstrate the effectiveness of the proposed technique, for detecting winding inter-turn insulation faults in operating three-phase transformers.
Document Type Article
Language English
delicious logo  facebook logo  linkedin logo  twitter logo 
degois logo
mendeley logo


    Financiadores do RCAAP

Fundação para a Ciência e a Tecnologia Universidade do Minho   Governo Português Ministério da Educação e Ciência Programa Operacional da Sociedade do Conhecimento EU