Solar XXI building PV systems: performance during the first two yeras of operation

Author(s): Rodrigues, Carlos cv logo 1 ; Viana, Susana cv logo 2 ; Joyce, António cv logo 3 ; Gonçalves, Helder cv logo 4 ; Silva, António Rocha e cv logo 5

Date: 2008

Persistent ID: http://hdl.handle.net/10400.9/1067

Origin: Repositório do LNEG

Subject(s): BIPV; Grid connected PV systems; PV micro-generation


Description
The purpose of this paper is to present the results obtained in the first two years of operation of the grid-connected photovoltaic (PV) systems installed in the named “Solar XXI” building. One PV system, made with multicrystalline silicon modules, has a peak power of 12 kW and was installed on the façade; another system made with amorphous silicon modules has a peak power of 6 kW and was installed in the surrounding park area near the building. From 1st February 2006 until 31 July 2008, the measured daily average, of the building electrical energy consumption, was about 75 kWh and the two PV systems produced in average about 72 % of this energy. The averaged measured Performance Ratio of the systems was about 0.84 for the PV Façade and about 0.76 for the PV in the Park.